Table 1. Three-phase non-directional overcurrent protection (PHxPTOC) main settings
Parameter Function Value (Range) Step
Start value PHLPTOC 0.05...5.00 × I n 0.01
PHHPTOC 0.10...40.00 × I n 0.01
PHIPTOC 1.00...40.00 × I n 0.01
Time multiplier PHLPTOC and PHHPTOC 0.05...15.00 0.01
Operate delay time PHLPTOC and PHHPTOC 40...200000 ms 10
PHIPTOC 20...200000 ms 10
Operating curve type 1 PHLPTOC

Definite or inverse time

Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

PHHPTOC

Definite or inverse time

Curve type: 1, 3, 5, 9, 10, 12, 15, 17

PHIPTOC Definite time
1 For further reference, see the Operation characteristics table