Table 1. Signal output X100: SO1
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at 48/110/220 V DC 1 A/0.25 A/0.15 A
Minimum contact load 100 mA at 24 V AC/DC
Table 2. Signal outputs and IRF output
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 15 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at 48/110/220 V DC 1 A/0.25 A/0.15 A
Minimum contact load 10 mA at 5 V AC/DC