| Characteristic | Value | |||
|---|---|---|---|---|
| Operation accuracy | Depending on the frequency of the measured voltage: f/fn = ±2 Hz | |||
|
±0.5% or ±0.002 × Un |
||||
| Suppression of harmonics |
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,… RMS: No suppression |
|||