Table 1. Non-directional earth-fault protection (EFxPTOC)
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz
EFLPTOC ±1.5% of the set value or ±0.002 × I n

EFHPTOC

and

EFIPTOC

±1.5% of set value or ±0.002 × I n

(at currents in the range of 0.1…10 × I n)

±5.0% of the set value

(at currents in the range of 10…40 × I n)

Start time , Minimum Typical Maximum

EFIPTOC:

I Fault = 2 × set Start value

I Fault = 10 × set Start value

16 ms

11 ms

19 ms

12 ms

23 ms

14 ms

EFHPTOC and EFLPTOC:

I Fault = 2 × set Start value

23 ms

26 ms

29 ms

Reset time Typically 40 ms
Reset ratio Typically 0.96
Retardation time <30 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode

±5.0% of the theoretical value or ±20 ms

Suppression of harmonics

RMS: No suppression

DFT: -50 dB at f = n × f n, where n = 2, 3, 4, 5,…

Peak-to-Peak: No suppression

1 Measurement mode = default (depends on stage), current before fault = 0.0 × I n, f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact
3 Maximum Start value = 2.5 × I n, Start value multiples in range of 1.5...20