Table 1. Lens sensor and optical fiber for arc protection
Description Value
Fiber optic cable including lens 1.5 m, 3.0 m or 5.0 m
Normal service temperature range of the lens -40...+100°C
Maximum service temperature range of the lens, max 1 h +140°C
Minimum permissible bending radius of the connection fiber 100 mm