Fuse failure supervision - Arc protection - Merging unit - Transformer protection - 2 winding - Product Guide - RET615 Transformer Protection and Control - 5.0 FP1 IEC - IEC - 24.05.2023

RET615 Product Guide

Depending on the chosen standard configuration, the relay includes fuse failure supervision functionality. The fuse failure supervision detects failures between the voltage measurement circuit and the relay. The failures are detected either by the negative sequence-based algorithm or by the delta voltage and delta current algorithm. Upon the detection of a failure, the fuse failure supervision function activates an alarm and blocks voltage-dependent protection functions from unintended operation.