Fuse failure supervision (SEQSPVC) - Arc protection - Merging unit - Transformer protection - 2 winding - Product Guide - RET615 Transformer Protection and Control - 5.0 FP1 IEC - IEC - 09.02.2023

RET615 Product Guide

Table 1. Fuse failure supervision (SEQSPVC)
Characteristic Value
Operate time 1 NPS function

U Fault = 1.1 × set Neg Seq voltage Lev

<33 ms

U Fault = 5.0 × set Neg Seq voltage Lev

<18 ms

Delta function

ΔU = 1.1 × set Voltage change rate

<30 ms

ΔU = 2.0 × set Voltage change rate

<24 ms

1 Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements