Circuit breaker failure protection (CCBRBRF) - Arc protection - Merging unit - Transformer protection - 2 winding - Product Guide - RET615 Transformer Protection and Control - Relion 615 series - 5.0 FP1 IEC - IEC - 11.10.2021

RET615 Product Guide

Table 1. Circuit breaker failure protection (CCBRBRF)
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz
±1.5% of the set value or ±0.002 × I n
Operate time accuracy ±1.0% of the set value or ±20 ms
Reset time Typically 40 ms
Retardation time <20 ms