Binary inputs - Arc protection - Merging unit - Transformer protection - 2 winding - Product Guide - RET615 Transformer Protection and Control - 5.0 FP1 IEC - IEC - 24.05.2023

RET615 Product Guide

Table 1. Binary inputs
Description Value
Operating range ±20% of the rated voltage
Rated voltage

24...250 V DC

Current drain 1.6...1.9 mA
Power consumption 31.0...570.0 mW
Threshold voltage 16...176 V DC
Reaction time

<3 ms