Three-phase voltage-dependent overcurrent protection (PHPVOC) - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Table 1. Three-phase voltage-dependent overcurrent protection (PHPVOC)
Characteristic Value
Operation accuracy

Depending on the frequency of the measured current and voltage:

fn ±2 Hz

Current:

±1.5% of the set value or ± 0.002 × In

Voltage:

±1.5% of the set value or ± 0.002 × Un

Start time 1 2 Typically 26 ms
Reset time Typically 40 ms
Reset ratio Typically 0.96
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the set value or ±20 ms
Suppression of harmonics -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
1 Measurement mode = default, current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact