Three-phase voltage-dependent overcurrent protection (PHPVOC) main settings - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Table 1. Three-phase voltage-dependent overcurrent protection (PHPVOC) main settings
Parameter Function Value (Range) Step
Start value PHPVOC 0.05...5.00 × In 0.01
Start value low PHPVOC 0.05...1.00 × In 0.01
Voltage high limit PHPVOC 0.01...1.00 × Un 0.01
Voltage low limit PHPVOC 0.01...1.00 × Un 0.01
Start value Mult PHPVOC 0.8...10.0 0.1
Time multiplier PHPVOC 0.05...15.00 0.01
Operating curve type 1 PHPVOC

Definite or inverse time

Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

Operate delay time PHPVOC 40...200000 ms 10
1 For further reference, see the Operation characteristics table