Three-phase directional overcurrent protection (DPHxPDOC) - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Table 1. Three-phase directional overcurrent protection (DPHxPDOC)
Characteristic Value
Operation accuracy Depending on the frequency of the current/voltage measured: f n ±2 Hz

DPHLPDOC

Current:

±1.5% of the set value or ±0.002 × I n

Voltage:

±1.5% of the set value or ±0.002 × U n

Phase angle: ±2°

DPHHPDOC

Current:

±1.5% of the set value or ±0.002 × I n

(at currents in the range of 0.1…10 × I n)

±5.0% of the set value

(at currents in the range of 10…40 × I n)

Voltage:

±1.5% of the set value or ±0.002 × U n

Phase angle: ±2°

Start time 1, 2 Minimum Typical Maximum
I Fault = 2.0 × set Start value

39 ms

43 ms

47 ms

Reset time Typically 40 ms
Reset ratio Typically 0.96
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode

±5.0% of the theoretical value or ±20 ms 3

Suppression of harmonics DFT: -50 dB at f = n × f n, where n = 2, 3, 4, 5,…
1 Measurement mode and Pol quantity = default, current before fault = 0.0 × I n, voltage before fault = 1.0 × U n, f n = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact
3 Maximum Start value = 2.5 × I n, Start value multiples in range of 1.5...20