| Parameter | Function | Value (Range) | Step |
|---|---|---|---|
| Start value | DPHLPDOC | 0.05...5.00 × In | 0.01 |
| DPHHPDOC | 0.10...40.00 × In | 0.01 | |
| Time multiplier | DPHxPDOC | 0.05...15.00 | 0.01 |
| Operate delay time | DPHxPDOC | 40...200000 ms | 10 |
| Operating curve type 1 | DPHLPDOC |
Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19 |
|
| DPHHPDOC |
Definite or inverse time Curve type: 1, 3, 5, 9, 10, 12, 15, 17 |
||
| Directional mode | DPHxPDOC |
1 = Non-directional 2 = Forward 3 = Reverse |
- |
| Characteristic angle | DPHxPDOC | -179...180° | 1 |
1 For further reference, see the Operating characteristics table