| Parameter | Function | Value (Range) | Step |
|---|---|---|---|
| Overload factor | MPTTR | 1.00...1.20 | 0.01 |
| Alarm thermal value | MPTTR | 50.0...100.0% | 0.1 |
| Restart thermal Val | MPTTR | 20.0...80.0% | 0.1 |
| Weighting factor p | MPTTR | 20.0...100.0% | 0.1 |
| Time constant normal | MPTTR | 80...4000 s | 1 |
| Time constant start | MPTTR | 80...4000 s | 1 |
| Env temperature mode | MPTTR |
1 = FLC Only 2 = Use input 3 = Set Amb Temp |
- |
| Env temperature Set | MPTTR | -20.0...70.0°C | 0.1 |
| Operation | MPTTR |
1 = on 5 = off |
- |