Synchronism and energizing check (SECRSYN) - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Table 1. Synchronism and energizing check (SECRSYN)
Characteristic Value
Operation accuracy Depending on the frequency of the voltage measured: f n ±1 Hz

Voltage:

±3.0% of the set value or ±0.01 × U n

Frequency:

±10 mHz

Phase angle:

±3°

Reset time <50 ms
Reset ratio Typically 0.96
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms