Stabilized and instantaneous differential protection for machines (MPDIF) - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion 615 series - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Table 1. Stabilized and instantaneous differential protection for machines (MPDIF)
Characteristic Value
Operation accuracy At the frequency f = fn
±3% of the set value or ±0.002 x In
Operate time 1, 2 Biased low stage Instantaneous high stage 3 Typical 40 ms (±10 ms) Typical 15 ms (±10 ms)
Reset time <40 ms
Reset ratio Typically 0.96
Retardation time <20 ms
1 Fn = 50 Hz, results based on statistical distribution of 1000 measurements
2 Includes the delay of the high speed power output contact
3 Ifault = 2 x High operate value