Table 1. Stabilized and instantaneous differential protection for machines (MPDIF) main settings
Parameter Function Value (Range) Step
Low operate value MPDIF 5...30 %Ir 1
High operate value MPDIF 100...1000 %Ir 10
Slope section 2 MPDIF 10...50% 1
End section 1 MPDIF 0...100 %Ir 1
End section 2 MPDIF 100...300 %Ir 1
DC restrain enable MPDIF 0 = False 1 = True -
CT connection type MPDIF 1 = Type 1 2 = Type 2 -
CT ratio Cor Line MPDIF 0.40...4.00 0.01
CT ratio Cor Neut MPDIF 0.40...4.00 0.01