Single-phase undervoltage protection (PHAPTUV) - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Table 1. Single-phase undervoltage protection (PHAPTUV)
Characteristic Value
Operation accuracy Depending on the frequency of the voltage measured: f n ±2 Hz
±1.5% of the set value or ±0.002 × U n
Start time 1, 2 Minimum Typical Maximum
U Fault = 0.9 × set Start value 64 ms

68 ms

71 ms

Reset time Typically 40 ms
Reset ratio Depends on the set Relative hysteresis
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3
Suppression of harmonics DFT: -50 dB at f = n × f n, where n = 2, 3, 4, 5,…
1 Start value = 1.0 × U n, Voltage before fault = 1.1 × U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact
3 Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20