| Parameter | Function | Value (Range) | Step |
|---|---|---|---|
| Start value | PHAPTUV | 0.05...1.20 × U n | 0.01 |
| Time multiplier | PHAPTUV | 0.05...15.00 | 0.01 |
| Operate delay time | PHAPTUV | 60...300000 ms | 10 |
| Operating curve type 1 | PHAPTUV |
Definite or inverse time Curve type: 5, 15, 21, 22, 23 |
|
1 For further reference, see the Operation characteristics table