Signal outputs - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Table 1. Signal output with high make and carry
Description Value 1
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time constant L/R <40 ms 1 A/0.25 A/0.15 A
Minimum contact load 100 mA at 24 V AC/DC
Table 2. Signal outputs and IRF output
Description Value 2
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 15 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at 48/110/220 V DC 1 A/0.25 A/0.15 A
Minimum contact load 10 mA at 5 V AC/DC
1

X100: SO1

X105: SO1, SO2, when any of the protection relays is equipped with BIO0005.

X115: SO1, SO2 when REF620 or REM620 is equipped with BIO0005.

2

X100: IRF,SO2

X105: SO3, SO4, when any of the protection relays is equipped with BIO0005

X115:SO3, SO4, when REF620 or REM620 is equipped with BIO0005