Sequence voltage measurement (VSMSQI) - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - 2.0 FP1 IEC - IEC - 09.02.2023

REM620 Product Guide

Table 1. Sequence voltage measurement (VSMSQI)
Characteristic Value
Operation accuracy

Depending on the frequency of the voltage measured: fn ±2 Hz

At voltages in range 0.01…1.15 × Un

±1.0% or ±0.002 × Un
Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…