Table 1. Rotor earth-fault protection (MREFPTOC) main settings
Parameter Function Value (Range) Step
Operate start value MREFPTOC 0.010. 2.000 × In 0.001
Alarm start value MREFPTOC 0.010. 2.000 × In 0.001
Operate delay time MREFPTOC 40...20000 ms 1
Alarm delay time MREFPTOC 40...200000 ms 1