Reverse power/directional overpower protection (DOPPDPR) main settings - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Table 1. Reverse power/directional overpower protection (DOPPDPR) main settings
Parameter Function Value (Range) Step
Start value DOPPDPR 0.01...2.00 × Sn 0.01
Operate delay time DOPPDPR 40...300000 ms 10
Directional mode DOPPDPR

2 = Forward

3 = Reverse

-
Power angle DOPPDPR -90...90° 1