Phase reversal protection (PREVPTOC) - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion 615 series - 2.0 FP1 IEC - IEC - 09.02.2023

REM620 Product Guide

Table 1. Phase reversal protection (PREVPTOC)
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz
±1.5% of the set value or ±0.002 × In
Start time 1, 2 Minimum Typical Maximum
IFault = 2.0 × set Start value

23 ms

25 ms

28 ms

Reset time Typically 40 ms
Reset ratio Typically 0.96
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
1 Negative-sequence current before = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact