Negative-sequence overvoltage protection (NSPTOV) - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Table 1. Negative-sequence overvoltage protection (NSPTOV)
Characteristic Value
Operation accuracy Depending on the frequency of the voltage measured: f n±2 Hz
±1.5% of the set value or ±0.002 × U n
Start time 1, 2 Minimum Typical Maximum

U Fault = 1.1 × set Start value

U Fault = 2.0 × set Start value

33 ms

24 ms

35 ms

26 ms

37 ms

28 ms

Reset time Typically 40 ms
Reset ratio Typically 0.96
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n × f n, where n = 2, 3, 4, 5,…
1 Negative-sequence voltage before fault = 0.0 × U n, f n = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact