| Characteristic | Value | |||
|---|---|---|---|---|
| Operation accuracy | Depending on the frequency of the measured current: fn ±2 Hz | |||
| ±1.5% of the set value or ±0.002 × In | ||||
| Start time 1, 2 | Minimum | Typical | Maximum | |
|
IFault = 1.1 × set Start detection A |
27 ms |
30 ms |
34 ms |
|
| Operate time accuracy | ±1.0% of the set value or ±20 ms | |||
| Reset ratio | Typically 0.90 | |||
1 Current before = 0.0 × In, fn = 50 Hz, overcurrent in one phase, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact