Loss of load supervision (LOFLPTUC) - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion 615 series - 2.0 FP1 IEC - IEC - 09.02.2023

REM620 Product Guide

Table 1. Loss of load supervision (LOFLPTUC)
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz
±1.5% of the set value or ±0.002 × In
Start time Typically 300 ms
Reset time Typically 40 ms
Reset ratio Typically 1.04
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms