High-impedance/flux-balance based differential protection for motors (MHZPDIF) - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion 615 series - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Table 1. High-impedance/flux-balance based differential protection for motors (MHZPDIF)
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz
±1.5% of the set value or 0.002 × In
Start time 1, 2 IFault = 2.0 × set Start Value (one phase fault) Minimum Typical Maximum
13 ms 17 ms 21 ms
IFault = 2.0 × set Start Value (three phases fault) 11 ms 14 ms 17 ms
Reset time <40 ms
Reset ratio Typically 0.96
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0% of the set value of ±20 ms
1 Measurement mode = “Peak-to-Peak”, current before fault = 0.0 × In, fn = 50 Hz, fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact