Environmental conditions - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - 2.0 FP1 IEC - IEC - 24.05.2023

REM620 Product Guide

Table 1. Environmental conditions
Description Value
Operating temperature range -25...+55ºC (continuous)
Short-time service temperature range -40...+85ºC (<16 h) 1, 2
Relative humidity <93%, non-condensing
Atmospheric pressure 86...106 kPa
Altitude Up to 2000 m
Transport and storage temperature range -40...+85ºC
1 Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2 For relays with an LC communication interface the maximum operating temperature is +70 ºC