Table 1. Energizing inputs
Description Value
Rated frequency 50/60 Hz
Current inputs Rated current, I n 0.2/1 A 1 1/5 A 2
Thermal withstand capability:
  • Continuously

4 A

20 A

  • For 1 s

100 A

500 A

Dynamic current withstand:
  • Half-wave value

250 A

1250 A

Input impedance <100 mΩ <20 mΩ
Voltage inputs Rated voltage 60...210 V AC
Voltage withstand:
  • Continuous
240 V AC
  • For 10 s
360 V AC
Burden at rated voltage <0.05 VA
1 Ordering option for residual current input
2 Residual current and/or phase current