| Description | Value | |
|---|---|---|
| Current sensor input | Rated current voltage | 75 mV ... 9000 mV 1 |
| Continuous voltage withstand | 125 V | |
| Input impedance at 50/60Hz | 2...3 MΩ 2 | |
| Voltage sensor input | Rated secondary voltage | 346 mV…1733 mV 3 |
| Continuous voltage withstand | 50 V | |
| Input impedance at 50/60Hz | 3 MΩ | |
| Description | Value | |
|---|---|---|
|
Current sensor input |
Rated current voltage |
75 mV ... 9000 mV 1 |
|
Continuous voltage withstand |
125 V |
|
|
Input impedance at 50/60Hz |
2 MΩ |
|
|
Voltage sensor input |
Rated secondary voltage |
346 mV…2339 mV 4 |
|
Continuous voltage withstand |
50 V |
|
|
Input impedance at 50/60Hz |
2 MΩ |
|
1 Equals the current range of 40 … 4000 A with 80A, 3mV/Hz Rogowski
2 Depending on the used nominal current (hardware gain)
3 Covers 6 kV … 30 kV sensors with division ratio of 10 000:1. Secondary voltages 600mV/√3 … 3 V / √3. Range up to 2 x Rated.
4 Covers 6 kV … 40.5 kV sensors with division ratio of 10 000:1. Secondary voltages 600mV/√3 … 4.05V / √3. Range up to 2 x Rated.