| Description | Type test value | Reference |
|---|---|---|
| 1 MHz/100 kHz burst disturbance test | IEC 61000-4-18 IEC 60255-26 IEEE C37.90.1-2012 |
|
|
2.5 kV | |
|
2.5 kV | |
| 3 MHz, 10 MHz and 30 MHz burst disturbance test | IEC 61000-4-18 IEC 60255-26 |
|
|
2.5 kV | |
| Electrostatic discharge test | IEC 61000-4-2 IEC 60255-26 IEEE C37.90.3-2001 |
|
|
8 kV | |
|
15 kV | |
| Radio frequency interference test | ||
| 10 V (rms) f = 150 kHz...80 MHz |
IEC 61000-4-6 IEC 60255-26 |
|
| 10 V/m (rms) f = 80...2700 MHz |
IEC 61000-4-3 IEC 60255-26 |
|
| 10 V/m f = 900 MHz 20 V/m (rms)f = 80...1000 MHz |
ENV 50204 IEC 60255-26 IEEE C37.90.2-2004 |
|
| Fast transient disturbance test | IEC 61000-4-4 IEC 60255-26 IEEE C37.90.1-2012 |
|
|
4 kV | |
| Surge immunity test | IEC 61000-4-5 IEC 60255-26 |
|
|
2 kV, line-to-earth | |
|
4 kV, line-to-earth 2 kV, line-to-line |
|
| Power frequency (50 Hz) magnetic field immunity test | IEC 61000-4-8 IEC 60255-26 |
|
|
300 A/m 1000 A/m |
|
| Pulse magnetic field immunity test |
1000 A/m
6.4/16 µs |
IEC 61000-4-9 |
| Damped oscillatory magnetic field immunity test | IEC 61000-4-10 | |
|
100 A/m | |
|
400 transients/s | |
| Voltage dips and short interruptions | 0%/50 ms Criterion A 40%/200 ms Criterion C 70%/500 ms Criterion C 0%/5000 ms Criterion C |
IEC 61000-4-11
IEC 61000-4-29 IEC 60255-26 |
| Power frequency immunity test | Binary inputs only | IEC 61000-4-16 IEC 60255-26, class A |
|
300 V rms | |
|
150 V rms | |
| Conducted common mode disturbances |
15 Hz...150 kHz
Test level 3 (10/1/10 V rms) |
IEC 61000-4-16 |
| Emission tests | EN 55011, class A IEC 60255-26 CISPR 11 CISPR 12 |
|
|
||
| 0.15...0.50 MHz | <79 dB (μV) quasi peak <66 dB (μV) average |
|
| 0.5...30 MHz | <73 dB (μV) quasi peak <60 dB (μV) average |
|
|
||
| 30...230 MHz | <40 dB (μV/m) quasi peak, measured at 10 m distance | |
| 230...1000 MHz | <47 dB (μV/m) quasi peak, measured at 10 m distance | |
| 1…3 GHz | <76 dB (μV/m) peak <56 dB (μV/m) average, measured at 3 m distance |
|
| 3…6 GHz | <80 dB (μV/m) peak <60 dB (μV/m) average, measured at 3 m distance |
|
|
AC component in DC (ripple) |
15% of rated DC, 100/120Hz, Criterion A |
IEC 61000-4-17
IEC 60255-26 |
|
Gradual shut down / start-up test |
Shut down time 60s Power off time 5 min Start-up time 60s |
IEC 60255-26 |