Directional reactive power undervoltage protection (DQPTUV) - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Table 1. Directional reactive power undervoltage protection (DQPTUV)
Characteristic Value
Operation accuracy Depending on the frequency of the measured current and voltage:

f n ±2 Hz

Reactive power range |PF| <0.71

Power:

±3.0% or ±0.002 × Q n

Voltage:

±1.5% of the set value or ±0.002 × U n

Start time 1, 2 Typically 46 ms
Reset time <50 ms
Reset ratio Typically 0.96
Operate time accuracy ±1.0% of the set value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n × f n, where n = 2, 3, 4, 5,…
1 Start value = 0.05 × S n, reactive power before fault = 0.8 × Start value, reactive power overshoot 2 times, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact