Current circuit supervision - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Current circuit supervision is used for detecting faults in the current transformer secondary circuits. On detecting of a fault the current circuit supervision function activates an alarm LED and blocks certain protection functions to avoid unintended operation. The current circuit supervision function calculates the sum of the phase currents from the protection cores and compares the sum with the measured single reference current from a core balance current transformer or from separate cores in the phase current transformers.