Circuit breaker failure protection (CCBRBRF) - Arc protection - Merging unit - Motor protection - Product Guide - REM620 Motor Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Product Guide

Table 1. Circuit breaker failure protection (CCBRBRF)
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz
±1.5% of the set value or ±0.002 × I n
Operate time accuracy ±1.0% of the set value or ±20 ms
Reset time 1 Typically 40 ms
Retardation time <20 ms
1 Trip pulse time defines the minimum pulse length