| Characteristic | Value |
|---|---|
| Operation accuracy | Depending on the frequency of the voltage measured: f n ±2 Hz |
|
Current: ±1.5% of the set value or ±0.002 × I n Voltage: ±1.5% of the set value or ±0.002 × Un |
|
| Operate time accuracy | ±1.0% of the set value or ±20 ms |
| Suppression of harmonics | DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,… |