Process bus - Arc protection - Merging unit - Motor protection - Application Manual - REM620 Motor Protection and Control - 2.0 FP1 IEC - IEC - 04.04.2023

REM620 Application Manual

Process bus IEC 61850-9-2 defines the transmission of Sampled Measured Values within the substation automation system. International Users Group created a guideline IEC 61850-9-2 LE that defines an application profile of IEC 61850-9-2 to facilitate implementation and enable interoperability. Process bus is used for distributing process data from the primary circuit to all process bus compatible devices in the local network in a real-time manner. The data can then be processed by any protection relay to perform different protection, automation and control functions.

UniGear Digital switchgear concept relies on the process bus together with current and voltage sensors. The process bus enables several advantages for the UniGear Digital like simplicity with reduced wiring, flexibility with data availability to all devices, improved diagnostics and longer maintenance cycles.

With process bus the galvanic interpanel wiring for sharing busbar voltage value can be replaced with Ethernet communication. Transmitting measurement samples over process bus brings also higher error detection because the signal transmission is automatically supervised. Additional contribution to the higher availability is the possibility to use redundant Ethernet network for transmitting SMV signals.

Figure 1. Process bus application of voltage sharing and synchrocheck
image/svg+xmlCommon EthernetStation bus (IEC 61850-8-1), process bus(IEC 61850-9-2 LE) and IEEE 1588 v2 time synchronizationGOOSESMVGOOSESMVSMVGOOSEGOOSESMVGOOSESMVSMVGOOSESMVGOOSE

The 620 series supports IEC 61850 process bus with sampled values of analog currents and voltages. The measured values are transferred as sampled values using the IEC 61850-9-2 LE protocol which uses the same physical Ethernet network as the IEC 61850-8-1 station bus. The intended application for sampled values is sharing the measured voltages from one 620 series protection relay to other devices with phase voltage based functions and 9-2 support.

The 620 series protection relays with process bus based applications use IEEE 1588 v2 Precision Time Protocol (PTP) according to IEEE C37.238-2011 Power Profile for high accuracy time synchronization. With IEEE 1588 v2, the cabling infrastructure requirement is reduced by allowing time synchronization information to be transported over the same Ethernet network as the data communications.

Figure 2. Example network topology with process bus, redundancy and IEEE 1588 v2 time synchronization
image/svg+xmlIEC 61850 HSRSMV trafficBackup 1588master clockManaged HSREthernet switchPrimaryIEEE 1588 v2 master clockSecondaryIEEE 1588 v2 master clock(optional)Managed HSREthernet switch

The process bus option is available for all 620 series protection relays equipped with phase voltage inputs. Another requirement is a communication card with IEEE 1588 v2 support (COM0031...COM0034 or COM0037). See the IEC 61850 engineering guide for detailed system requirements and configuration details.