Functional diagrams for extra functions - Arc protection - Merging unit - Motor protection - Application Manual - REM620 Motor Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Application Manual

Additional functions are available in the relay default content but they are not preengineered to be part of the default configuration. The functions can be engineered into use.

Figure 1. Flux-balance based differential protection for motors
image/svg+xmlHIGH-IMPEDANCE OR FLUX-BALANCE BASED DIFFERENTIAL PROTECTION FOR MOTORSMHZPDIF13dIHi>M(1)87MH(1)ID_ASTARTOPERATEID_BID_CBLOCK

One high-impedance or flux-balance based differential protection for motors MHZPDIF1 is offered. MHZPDIF provides the winding short-circuit and earth-fault protection for motors. Due to the capability to manage through-faults with a heavy current transformer (CT) saturation, the high-impedance or flux-balance principle has been commonly used for differential protection. MPDIF1 can alternatively be used for this function. For detailed information, see the technical manual.

Figure 2. Rotor earth-fault protection
image/svg+xmlROTOR EARTH-FAULT PROTECTIONMREFPTOC1Io>R(1)64R(1)IoSTARTOPERATEBLOCKALARM

One rotor earth-fault protection function MREFPTOC1 is offered. MREFPTOC is used to detect an earth fault in the rotor circuit of synchronous machines. For detailed information, see the technical manual.