Default disturbance recorder settings - Arc protection - Merging unit - Motor protection - Application Manual - REM620 Motor Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Application Manual

Table 1. Default disturbance recorder settings binary channels
Channel Id text Level trigger mode
1 PHLPTOC1_START Positive or Rising
2 PHHPTOC1_START Positive or Rising
3 PHHPTOC2_START Positive or Rising
4 PHIPTOC1_START Positive or Rising
5 DPHLPDOC1_START Positive or Rising
6 DPHHPDOC1_START Positive or Rising
7 DPHHPDOC2_START Positive or Rising
8 PHxPTOC or DPHxPDOC_OPERATE Level trigger off
9 EFLPTOC1_START Positive or Rising
10 EFHPTOC1_START Positive or Rising
11 EFIPTOC1_START Positive or Rising
12 DEFLPDEF1_START Positive or Rising
13 DEFHPDEF1_START Positive or Rising
14 EFxPTOC or DEFxPDEF_OPERATE Level trigger off
15 ROVPTOV1/2/3_START Positive or Rising
16 ROVPTOV1/2/3_OPERATE Level trigger off
17 PHPTUV or PHPTOV or PSPTUV or NSPTOV_START Positive or Rising
18 PHPTUV or PHPTOV or PSPTUV or NSPTOV_OPERATE Level trigger off
19 FRPFRQ_START Positive or Rising
20 FRPFRQ_OPERATE Level trigger off
21 MNSPTOC1_START Positive or Rising
22 MNSPTOC2_START Positive or Rising
23 MNSPTOC1/2_BLK_RESTART Level trigger off
24 MNSPTOC1/2_OPERATE Level trigger off
25 LOFLPTUC1_START Positive or Rising
26 LOFLPTUC2_START Positive or Rising
27 LOFPTUC1/2_OPERATE Level trigger off
28 MPTTR1_ALARM Level trigger off
29 MPTTR1_BLK_RESTART Level trigger off
30 MPTTR1_OPERATE Level trigger off
31 PREVPTOC1_START Positive or Rising
32 PREVPTOC1_OPERATE Level trigger off
33 ESMGAPC_ST_EMERG_ENA Level trigger off
34 MPDIF1_OPERATE Positive or Rising
35 MPDIF1_OPR_LS Level trigger off
36 MPDIF1_OPR_HS Level trigger off
37 MPDIF1_INT_BLKD Level trigger off
38 JAMPTOC1_OPERATE Positive or Rising
39 STTPMSU1_MOT_START Positive or Rising
40 STTPMSU1_LOCK_START Level trigger off
41 STTPMSU1_OPR_IIT Positive or Rising
42 STTPMSU1_OPR_STALL Positive or Rising
43 ARCSARC1/2/3_ARC_FLT_DET Level trigger off
44 ARCSARC1_OPERATE Positive or Rising
45 ARCSARC2_OPERATE Positive or Rising
46 ARCSARC3_OPERATE Positive or Rising
47 SEQSPVC1_FUSEF_3PH Level trigger off
48 SEQSPVC1_FUSEF_U Level trigger off
49 CCSPVC1_FAIL Level trigger off
50 CCBRBRF1_TRRET Level trigger off
51 CCBRBRF1_TRBU Level trigger off
52 CB Closed Level trigger off
53 CB Open Level trigger off
54 Emergency Start Enable Level trigger off
55 Bus MCB Open Level trigger off
56 Line MCB Open Level trigger off
57 External Restart Inhibit Level trigger off
58 Speed Switch Level trigger off
59 MDSOPT1_ALARM Level trigger off
60 MAPGAPC1_START Positive or Rising
61 MAPGAPC2_START Positive or Rising
62 MAPGAPC3_START Positive or Rising
63 MAPGAPC1/2/3_OPERATE Level trigger off
64 FKEY K9_DR Manual Trigger Positive or Rising

Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.

Table 2. Default analog channel selection and text settings
Channel Selection and text
1 IL1
2 IL2
3 IL3
4 IL1B 1
5 IL2B 1
6 IL3B 1
7 Io
8 Uo
9 U1
10 U2
11 U3
12 U1B
1 ILxB in this table refers to ILx_N in the connection diagrams.