| Analog input | Default usage | Connector pins |
|---|---|---|
| IL1_N | Phase A current, neutral side | X120:1,2 |
| IL2_N | Phase B current, neutral side | X120:3,4 |
| IL3_N | Phase C current, neutral side | X120:5,6 |
| IL1 | Phase A current, terminal side | X120:7,8 |
| IL2 | Phase B current, terminal side | X120:9,10 |
| IL3 | Phase C current, terminal side | X120:11,12 |
| Io | Residual current | X120:13,14 |
| U_SYN | Phase-to-phase voltage U12, terminal side | X130:9,10 |
| U1 | Phase-to-phase voltage U12, bus side | X130:11,12 |
| U2 | Phase-to-phase voltage U23, bus side | X130:13,14 |
| U3 | Phase-to-phase voltage U31, bus side | X130:15,16 |
| Uo | Residual voltage, bus side | X130:17,18 |
| RTD1 | Motor winding U temperature | X110:9,10 |
| RTD2 | Motor winding V temperature | X110:11,12 |
| RTD3 | Motor winding W temperature | X110:13,14 |
| RTD4 | Motor cooling air temperature | X110:17,18 |
| RTD5 | Motor bearing temperature | X110:19,20 |
| RTD6 | Motor ambient temperature | X110:21,22 |
| Binary input | Default usage | Connector pins |
|---|---|---|
| X105-BI1 | Rotation direction | X105:1,2 |
| X105-BI2 | Emergency start enable | X105:3,4 |
| X105-BI3 | External restart inhibit | X105:5,6 |
| X105-BI4 | External trip | X105:7,6 |
| X105-BI5 | Emergency start | X105:8,9 |
| X105-BI6 | Emergency stop | X105:10,9 |
| X105-BI7 | Line MCB open position indication | X105:11,12 |
| X105-BI8 | - | X105:13,12 |
| X115-BI1 | Circuit breaker closed position indication | X115:1,2 |
| X115-BI2 | Circuit breaker open position indication | X115:3,4 |
| X115-BI3 | Circuit breaker low gas pressure alarm | X115:5,6 |
| X115-BI4 | Circuit breaker spring charged indication | X115:7,6 |
| X115-BI5 | Earthing switch 1 closed position indication | X115:8,9 |
| X115-BI6 | Earthing switch 1 open position indication | X115:10,9 |
| X115-BI7 | Speed switch (motor running) | X115:11,12 |
| X115-BI8 | Bus MCB open position indication | X115:13,12 |
| X130-BI1 | Disconnector 1 closed position indication | X130:1,2 |
| X130-BI2 | Disconnector 1 open position indication | X130:3,4 |
| X130-BI3 | Disconnector 2 closed position indication | X130:5,6 |
| X130-BI4 | Disconnector 2 open position indication | X130:7,8 |
| Binary input | Default usage | Connector pins |
|---|---|---|
| X100-PO1 | Restart enable | X100:6,7 |
| X100-PO2 | Breaker failure backup trip to upstream breaker | X100:8,9 |
| X100-SO1 | General start indication | X100:10,11,(12) |
| X100-SO2 | General operate indication | X100:13,14 |
| X100-PO3 | Open circuit breaker/trip | X100:15-19 |
| X100-PO4 | Close circuit breaker | X100:20-24 |
| X115-SO1 | Motor startup indication | X115:14-16 |
| X115-SO2 | Open command (for contactor applications) | X115:17-19 |
| X115-SO3 | Thermal overload alarm | X115:20-22 |
| X115-SO4 | Motor differential protection operate alarm | X115:23,24 |
| LED | Default usage | Label description |
|---|---|---|
| 1 | Motor differential protection biased stage operate | Diff. prot. biased low stage |
| 2 | Motor differential protection instantaneous stage operate | Diff. prot. inst. stage |
| 3 | Short circuit protection operate | Short circuit protection |
| 4 | Combined protection indication of the other protection functions | Combined Protection |
| 5 | Thermal overload protection operate | Thermal Overload for Motors |
| 6 | Motor restart inhibit | Motor restart inhibit |
| 7 | Circuit breaker failure protection backup protection operate | Breaker failure protection |
| 8 | Circuit breaker condition monitoring alarm | CB condition monitoring |
| 9 | Supervision alarm | Supervision |
| 10 | Emergency start enabled | Emergency start enabled |
| 11 | Arc fault detected | Arc detected |
| FK/SPCGAPC number | Default usage | Operation mode | Pulsed length |
|---|---|---|---|
| 1 | Setting Group 1 Enabled | Pulsed | 150 ms |
| 2 | Setting Group 2 Enabled | Pulsed | 150 ms |
| 3 | Setting Group 3 Enabled | Pulsed | 150 ms |
| 4 | Setting Group 4 Enabled | Pulsed | 150 ms |
| 5 | Setting Group 5 Enabled | Pulsed | 150 ms |
| 6 | Setting Group 6 Enabled | Pulsed | 150 ms |
| 7 | - | Off | 1000 ms |
| 8 | Emergency Start | Pulsed | 150 ms |
| 9 | Disturbance Recorder Manual Trigger | Pulsed | 150 ms |
| 10 | Trip Lockout Reset | Pulsed | 150 ms |
| 11 | Circuit Breaker Block Bypass | Toggle | 1000 ms |
| 12 | Restart Inhibit | Toggle | 1000 ms |
| 13 | - | Off | 1000 ms |
| 14 | - | Off | 1000 ms |
| 15 | - | Off | 1000 ms |
| 16 | - | Off | 1000 ms |