Connection of SMVRCV to ULTVTR2 - Arc protection - Merging unit - Motor protection - Application Manual - REM620 Motor Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Application Manual

Figure 1. Connection of SMVRCV to ULTVTR2 in Application Configuration
image/svg+xmlSMVRCVUL1UL2UL3UoULTVTR2[2]_ALARMULTVTR2[2]_WARNINGULTVTR2UL1UL2UL3MINCB_OPENALARMWARNING

When SMVRCV is connected to ULTVTR2 in the Application Configuration tool, ULTVTR2 is disconnected from the physical channel U_SYN and uses UL1 voltage from the received IEC 61850-9-2 LE sample value. All functions which have U_SYN input begin working with the IEC 61850-9-2 LE sample value.

Note: Only UL1 must be connected between SMVRCV and ULTVTR2 in the Application Configuration tool.
Note: The IEC 61850-9-2 LE stream always contains UL1, UL2, UL3 and Uo. When U_SYN as a single channel input is received from IEC 61850-9-2 LE, the setting VT connection in Configuration > Analog inputs > Voltage (3UB,VT)// must be “UL1”.
Figure 2. ULTVTR2 uses UL1 voltage from received IEC 61850-9-2 LE sample value
image/svg+xmlULTVTR2ULTVTR1RESTVTR1Uo3USECRSYN1PHAPTOV1PHPTOV1ROVPTOV1*Measured Uo9-2LEX1309101112U_SYN1314U11516U21718U3Uo60 -N210V60 -N210V60 -N210V60 -N210V60 -N210V