Connection of SMVRCV to ULTVTR1 - Arc protection - Merging unit - Motor protection - Application Manual - REM620 Motor Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Application Manual

Figure 1. Connection of SMVRCV to ULTVTR1 in Application Configuration
image/svg+xmlULTVTR1UL1UL2UL3MINCB_OPENALARMWARNINGSMVRCVUL1UL2UL3UoULTVTR1[1]_ALARMULTVTR1[1]_WARNING

When SMVRCV is connected to ULTVTR1 in the Application Configuration tool, ULTVTR1 is disconnected from the physical channels U1, U2 and U3 and uses three phase voltages from the received IEC 61850-9-2 LE sample value. All functions which have 3U input begin working with the IEC 61850-9-2 LE sample value.

Note: All three signals UL1, UL2 and UL3 must be connected between SMVRCV and ULTVTR1 in the Application Configuration tool.
Note: ULTVTR2, SECRSYN1 and VAMMUX2 cannot be used in this configuration.
Figure 2. ULTVTR1 uses three phase voltages from received IEC 61850-9-2 LE sample value
image/svg+xmlULTVTR1ULTVTR2SECRSYN1VAMMXU29-2LEPHPTOV1ROVPTOV1*Calculated UoX13145IL178U1X13245IL278U2X13345IL378U3