Connection of SMVRCV to RESTVTR1 - Arc protection - Merging unit - Motor protection - Application Manual - REM620 Motor Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023

REM620 Application Manual

Figure 1. Connection of SMVRCV to RESTVTR1 in Application Configuration
image/svg+xmlSMVRCVUL1UL2UL3UoRESTVTR1UoALARMWARNINGRESTVTR1[1]_ALARMRESTVTR1[1]_WARNING

When SMVRCV is connected to RESTVTR1 in the Application Configuration tool, RESTVTR1 is disconnected from the physical channel Uo and uses residual voltages from the received IEC 61850-9-2 LE sample value. All functions which have Uo input begin working with the IEC 61850-9-2 LE sample value.

Figure 2. RESTVTR1 uses residual voltages from received IEC 61850-9-2 LE sample value
image/svg+xmlULTVTR2ULTVTR1RESTVTR1Usyn3USECRSYN1PHAPTOV1PHPTOV1ROVPTOV1*Measured Uo9-2LEX1309101112U_SYN1314U11516U21718U3Uo60 -N210V60 -N210V60 -N210V60 -N210V60 -N210V