Connection of SMVRCV to RESTVTR1 - Arc protection - Merging unit - Motor protection - Application Manual - REM620 Motor Protection and Control - 2.0 FP1 IEC - IEC - 01.06.2023
Figure 1. Connection of SMVRCV to RESTVTR1 in Application Configuration
When SMVRCV is connected to RESTVTR1 in the Application Configuration tool, RESTVTR1 is disconnected from the physical channel Uo and uses residual voltages from the received IEC 61850-9-2 LE sample value. All functions which have Uo input begin working with the IEC 61850-9-2 LE sample value.
Figure 2. RESTVTR1 uses residual voltages from received IEC 61850-9-2 LE sample value