If extra control functions intended for controllable primary devices are added to the configuration, additional binary inputs and/or outputs are needed to complement the default configuration.

If the number of inputs and/or outputs in a default configuration is not sufficient, it is possible either to modify the chosen default configuration in order to release some binary inputs or binary outputs which have originally been configured for other purposes, or to connect an external input/output module, for example RIO600, to the protection relay.

The external I/O module’s binary inputs and outputs can be used for the less time-critical binary signals of the application. The integration enables releasing some initially reserved binary inputs and outputs of the protection relay’s default configuration.

The suitability of the protection relay’s binary outputs which have been selected for primary device control should be carefully verified, for example make and carry and breaking capacity. If the requirements for the primary device control circuit are not met, using external auxiliary relays should be considered.