Parameter values remain unchanged for all the functions listed in Versioned Functions and Hardwares list. Parameter values remain unchanged also for the functions not listed in the migration report, that is, the functions that have the same version in both the product versions.
Set the parameter values again for all the needed functions.
  • All functions listed in Obsolete Functions and Hardwares.
  • All parameters for which the migration failed. See the migration report for failed parameters.
  • Parameters of the DNP3 related functions that are reset to default values in migration. Restore the original parameters.
Note: Note that some functions may have new settings.