Importing a 615 series protection relay in a COM600S project - Grid automation - Engineering Manual - REC615 Grid Automation Protection and Control - RER615 Grid Automation Protection and Control - 2.0 - IEC - ANSI - 28.04.2023

REC615 and RER615 Engineering Manual

  1. Create a PCM600 project including several IEDs.
    Figure 1. Creating a PCM600 project including several IEDs
    image/svg+xml
  2. Export the SCD file from PCM600.

    In the Plant structure view, select the substation, right-click and select Export.

    Figure 2. Exporting SCD file from PCM600 and importing it to SAB600
    image/svg+xml
  3. Import the SCD configuration into the SAB600 project.
    In the Project Explorer view, right-click the IEC61850 OPC Server object and select SCL Import.
    Figure 3. Importing the SCD configuration into the SAB600 project
    image/svg+xml
  4. In the SCL Import view, click Select File to select the SCD file exported from PCM600.
    Figure 4. Creating a new IED into SAB600 project
    image/svg+xml
  5. Check the default settings in the SCL Import view and change the settings if they are not suitable.

    The default settings in the SCL Import dialog should be correct in most cases.

  6. Click Import to import the SCD file.
  7. Check the IP address on the IEC 61850 subnetwork and change it if needed.
    When the SCD file is directly exported from PCM600, it uses the IP address of the PCM600 computer, not the COM600S.

The communication towards the protection relays is now ready. For information on how to finalize the single-line diagram and enable parameter setting through COM600S HMI, see COM600S documentation.