Function | IEC 61850 | Logical device | Logical nodes in Ver.5.0 FP1 | Logical nodes in Ver.5.0 or older |
---|---|---|---|---|
Protection | ||||
Protection LLN0 |
Protection |
LD0 |
LLN0 LPHD LINF LDEV |
LLN0 LPHD IHMI GSAL |
Three-phase non-directional overcurrent protection, low stage |
PHLPTOC |
LD0 |
PHLPTOC |
PHLPTOC |
Three-phase non-directional overcurrent protection, low stage |
FPHLPTOC |
LD0 |
FPHLPTOC |
FPHLPTOC |
Three-phase non-directional overcurrent protection, high stage |
PHHPTOC |
LD0 |
PHHPTOC |
PHHPTOC |
Three-phase non-directional overcurrent protection, instantaneous stage |
PHIPTOC |
LD0 |
PHIPTOC |
PHIPTOC |
Three-phase directional overcurrent protection, low stage |
DPHLPDOC |
LD0 |
DPHLPTOC DPHLRDIR |
DPHLPTOC DPHLRDIR |
Three-phase directional overcurrent protection, low stage |
FDPHLPDOC |
LD0 |
FDPHLPTOC DPHLRDIR FDPHLRDIR |
FDPHLPTOC DPHLRDIR FDPHLRDIR |
Three-phase directional overcurrent protection, high stage |
DPHHPDOC |
LD0 |
DPHHPTOC DPHHRDIR |
DPHHPTOC DPHHRDIR |
Non-directional earth-fault protection, low stage |
EFLPTOC |
LD0 |
EFLPTOC |
EFLPTOC |
Non-directional earth-fault protection, high stage |
EFHPTOC |
LD0 |
EFHPTOC |
EFHPTOC |
Non-directional earth-fault protection, instantaneous stage |
EFIPTOC |
LD0 |
EFIPTOC |
EFIPTOC |
Directional earth-fault protection, low stage |
DEFLPDEF |
LD0 |
DEFLPTOC DEFLRDIR |
DEFLPTOC DEFLRDIR |
Directional earth-fault protection, low stage |
FDEFLPDEF |
LD0 |
FDEFLPTOC FDEFLRDIR |
FDPHLPTOC DPHLRDIR FDPHLRDIR |
Directional earth-fault protection, high stage |
DEFHPDEF |
LD0 |
DEFHPTOC DEFHRDIR |
DEFHPTOC DEFHRDIR |
Admittance-based earth-fault protection |
EFPADM |
LD0 |
EFPADM |
EFPADM |
Wattmetric-based earth-fault protection |
WPWDE |
LD0 |
WRDIR WPSDE WMMXU |
WRDIR WPSDE WMMXU |
Transient/intermittent earth-fault protection |
INTRPTEF |
LD0 |
INTRPTEF |
INTRPTEF |
Harmonics-based earth-fault protection |
HAEFPTOC |
LD0 |
HAEFPTOC HAEFMHAI |
HAEFPTOC HAEFMHAI |
Multifrequency admittance-based earth-fault protection |
MFADPSDE |
LD0 |
MFADPSDE MFADRDIR |
|
Non-directional (cross-country) earth-fault protection, using calculated Io |
EFHPTOC |
LD0 |
EFHPTOC |
EFHPTOC |
Negative-sequence overcurrent protection |
NSPTOC |
LD0 |
NSPTOC |
NSPTOC |
Phase discontinuity protection |
PDNSPTOC |
LD0 |
PDNSPTOC |
PDNSPTOC |
Residual overvoltage protection |
ROVPTOV |
LD0 |
ROVPTOV |
ROVPTOV |
Three-phase undervoltage protection |
PHPTUV |
LD0 |
PHPTUV |
PHPTUV |
Three-phase overvoltage protection |
PHPTOV |
LD0 |
PHPTOV |
PHPTOV |
Positive-sequence undervoltage protection |
PSPTUV |
LD0 |
PSPTUV |
PSPTUV |
Negative-sequence overvoltage protection |
NSPTOV |
LD0 |
NSPTOV |
NSPTOV |
Loss of phase (undercurrent) |
PHPTUC |
LD0 |
PHPTUC |
|
Frequency protection |
FRPFRQ |
LD0 |
FRPTRC FRPTOF FRPTUF FRPFRC |
FRPTRC FRPTOF FRPTUF FRPFRC |
Three-phase thermal protection for feeders, cables and distribution transformers |
T1PTTR |
LD0 |
T1PTTR |
T1PTTR |
Circuit breaker failure protection |
CCBRBRF |
LD0 |
CCBRBRF |
CCBRBRF |
Three-phase inrush detector |
INRPHAR |
LD0 |
INRPHAR |
INRPHAR |
Master trip |
TRPPTRC |
LD0 |
TRPPTRC |
TRPPTRC |
Multipurpose protection |
MAPGAPC |
LD0 |
MAPGAPC |
MAPGAPC |
Load-shedding and restoration |
LSHDPFRQ |
LD0 |
LSHDPTRC LSHDPTOF LSHDPTUF LSHDPFRC |
LSHDPTRC LSHDPTUF LSHDPFRC |
Fault locator |
SCEFRFLO |
LD0 |
SCEFRFLO SCEFZLIN SCEF2ZLIN SCEF3ZLIN FLORFRC |
SCEFRFLO FLOMSTA |
Phase power directional function |
DPSRDIR |
LD0 |
DPSRDIR |
|
Power quality | ||||
Current total demand distortion |
CMHAI |
LD0 |
CMHAI |
CMHAI |
Voltage total harmonic distortion |
VMHAI |
LD0 |
VMHAI |
VMHAI |
Voltage variation |
PHQVVR |
LD0 |
PHQVVR PH2QVVR PH3QVVR QVVRQRC QVV2RQRC QVV3RQRC |
PHQVVR PH2QVVR PH3QVVR QVVMSTA QVV2MSTA QVV3MSTA |
Voltage unbalance |
VSQVUB |
LD0 |
VSQVUB QVU1RQRC QVU2RQRC QVU3RQRC |
|
Control | ||||
Local/remote control function block |
Control |
CTRL |
LLN0 LPHD1 |
LLN0 LPHD1 |
Circuit breaker control |
CBXCBR |
CTRL |
CBCSWI CBCILO CBXCBR |
CBCSWI CBCILO CBXCBR |
Disconnector control |
DCXSWI |
CTRL |
DCCSWI DCCILO DCXSWI |
DCCSWI DCCILO DCXSWI |
Disconnector position indication |
DCSXSWI |
CTRL |
DCSXSWI |
DCSXSWI |
Earthing switch indication |
ESSXSWI |
CTRL |
ESSXSWI |
ESSXSWI |
Autoreclosing |
DARREC |
LD0 |
DARREC |
DARREC |
Synchronism and energizing check |
SECRSYN |
LD0 |
SECRSYN |
SECRSYN |
Automatic transfer switch |
ATSABTC |
LD0 |
ATSABTC |
ATSABTC |
Condition monitoring | ||||
Circuit-breaker condition monitoring |
SSCBR1 |
LD0 |
SSCBR1 SPH1SCBR SPH2SCBR SPH3SCBR SSOPM SSIMG |
SSCBR1 |
Trip circuit supervision |
TCSSCBR |
LD0 |
TCSSCBR |
TCSSCBR |
Current circuit supervision |
CCSPVC |
LD0 |
CCSPVC |
CCRDIF |
Fuse failure supervision |
SEQSPVC |
LD0 |
SEQSPVC |
SEQRFUF |
Runtime counter for machines and devices |
MDSOPT |
LD0 |
MDSOPT |
MDSOPT |
Voltage presence |
PHSVPR |
LD0 |
PHSVPR |
PHSVPR |
Measurement | ||||
Disturbance recorder |
RDRE |
LD0 |
DR_LLN0 RDRE_type RADR_type RBDR_type LPHD_M |
DR_LLN0 RDRE_type RADR_type RBDR_type LPHD_M |
Load profile record |
LDPRLRC |
LD0 |
LDPRLRC |
LDPMSTA |
Fault record |
FLTRFRC |
LD0 |
FLTRFRC |
FLTMSTA |
Three-phase current measurement |
CMMXU |
LD0 |
CMMXU CAVMMXU CMAMMXU CMIMMXU |
CMMXU CMSTA |
Phase sequence current measurement |
CSMSQI |
LD0 |
CSMSQI |
CSMSQI |
Residual current measurement |
RESCMMXU |
LD0 |
RESCMMXU RCAVMMXU RCMAMMXU RCMIMMXU |
RESCMMXU RESCMSTA |
Three-phase voltage measurement |
VMMXU |
LD0 |
VMMXU VAVMMXU |
VMMXU VMSTA |
Residual voltage measurement |
RESVMMXU |
LD0 |
RESVMMXU RVAVMMXU RVMAMMXU RVMIMMXU |
RESVMMXU RESVMSTA |
Phase sequence voltage measurement |
VSMSQI |
LD0 |
VSMSQI |
VSMSQI |
Three-phase power and energy measurement |
PEMMXU |
LD0 |
PEMMXU PEMMTR PEAVMMXU PEMAMMXU PEMIMMXU |
PEMMXU PEMMTR PEMSTA |
Single-phase power and energy measurement |
SPEMMXU |
LD0 |
SPEMMXU SPE1MMTR SPE2MMTR SPE3MMTR SPEAVMMXU SPEMAMMXU SPEMIMMXU |
|
Frequency measurement |
FMMXU |
LD0 |
FMMXU |
FMMXU |
RTD/mA measurement X130 (AIM+RTD) |
XARGGIO130 |
LD0 |
XARGGIO130 |
XARGGIO130 |
Instrument transformers and sensors | ||||
Three-phase current transformer |
ILTCTR |
LD0 |
IL1TCTR IL2TCTR IL3TCTR |
IL1TCTR IL2TCTR IL3TCTR |
Three-phase voltage transformer |
ULTVTR |
LD0 |
UL1TVTR UL2TVTR UL3TVTR |
UL1TVTR UL2TVTR UL3TVTR |
Residual current transformer |
RESTCTR |
LD0 |
RESTCTR |
RESTCTR |
Residual voltage transformer |
RESTVTR |
LD0 |
RESTVTR |
RESTVTR |
Communication | ||||
IEC 61850-9-2 LE sampled value sending |
SMVSENDER |
MU01 |
LLN0 LPHD1 I01ATCTR1 I01BTCTR2 I01CTCTR3 I01NTCTR4 U01ATVTR1 U01BTVTR2 U01CTVTR3 U01NTVTR4 |
LLN0 LPHD1 I01ATCTR1 I01BTCTR2 I01CTCTR3 I01NTCTR4 U01ATVTR1 U01BTVTR2 U01CTVTR3 U01NTVTR4 |
IEC 61850-9-2 LE sampled value receiving (voltage sharing) |
SMVRCV |
MU01 |
SMVLSVS |
|
Redundant Ethernet channel supervision |
RCHLCCH |
LD0 |
RCHLCCH |
|
Ethernet channel supervision |
SCHLCCH |
LD0 |
SCHLCCH |
|
Serial port supervision |
SERLCCH |
LD0 |
SERLCCH |
|
Human machine interface |
IHMI |
LD0 |
IHMI |
IHMI |
General security application |
GSAL |
LD0 |
GSAL |
GSAL |
Time synchronization and local time |
GNRLLTMS |
LD0 |
GNRLLTMS 1 GNRLLTIM |
GNRLLTMS |
Controllable logic | ||||
Minimum pulse timer |
TPGAPC |
TPGAPC |
TPGAPC |
|
Minimum pulse timer |
TPSGAPC |
TPSGAPC |
TPSGAPC |
|
Minimum pulse timer |
TPMGAPC |
TPMGAPC |
TPMGAPC |
|
Pulse timer |
PTGAPC |
PTGAPC |
PTGAPC |
|
Time delay off |
TOFGAPC |
TOFGAPC |
TOFGAPC |
|
Time delay on |
TONGAPC |
TONGAPC |
TONGAPC |
|
Set-reset |
SRGAPC |
SRGAPC |
SRGAPC |
|
Move |
MVGAPC |
MVGAPC |
MVGAPC |
|
Generic control point |
SPCGAPC |
SPCGAPC |
SPCGGIO |
|
Remote generic control points |
SPCRGAPC |
LD0 |
SPCRGAPC |
SPCRGAPC |
Local generic control points |
SPCLGAPC |
LD0 |
SPCLGAPC |
SPCLGAPC |
Generic up-down counters |
UDFCNT |
LD0 |
UDFCNT |
UDFCNT |
Analog value scaling |
SCA4GAPC |
SCA4GAPC |
SCA4GAPC |
|
Integer value move |
MVI4GAPC |
MVI4GAPC |
MVI4GAPC |
|
Daily timer function |
DTMGAPC |
LD0 |
DTMGAPC |
|
Programmable buttons (4 buttons) |
FKEY4GGIO |
LD0 |
FKEY4GGIO |
|
Protocols | ||||
IEC 61850 |
MMSLPRT |
LD0 |
MMSLPRT |
MMSGGIO |
GOOSE |
GSELPRT |
LD0 |
GSELPRT |
GSEGGIO |
MODBUS |
MBSLPRT |
LD0 |
MBSLPRT |
MBSLPRT |
DNP 3.0 |
DNPLPRT |
LD0 |
DNPLPRT |
DNPLPRT |
IEC 101/104 |
I5CLPRT |
LD0 |
I5CLPRT |
I5CLPRT |
Hardware | ||||
PSM (X100) card |
X100 (PSM) |
LD0 |
XGGIO100 |
XGGIO100 |
BIO (X110) card |
X110 (BIO) |
LD0 |
XGGIO110 |
XGGIO110 |
AIM (X120) 4CT with Io |
X120 (AIM) |
LD0 |
XGGIO120 |
XGGIO120 |
AIM (X120) 4CT with Uo |
X120 (AIM) |
LD0 |
XGGIO120 |
XGGIO120 |
AIM (X120) 7CT with Io |
X120 (AIM2) |
LD0 |
XAGGIO120 |
XAGGIO120 |
AIM (X120) 4CT_3VT with sensitive Io |
X120 (AIM2) |
LD0 |
XAGGIO120 |
XAGGIO120 |
AIM (X130) 5 VT |
X130 (AIM) |
LD0 |
XAGGIO130 |
XAGGIO130 |
AIM (X130) 5 VT, 2RTD and 1mA |
X130 (AIM +RTD) |
LD0 |
XARGGIO130 |
XARGGIO130 |
SIM (X130) sensor input module |
X130 (SIM) |
LD0 |
XSGGIO130 |
XSGGIO130 |
SIM (X130) 3Is_3Us with sensitive Io |
X130 (SIM) |
LD0 |
XSGGIO130 |
XSGGIO130 |
SIM (X130) 3Is_3Us_3VT with sensitive Io |
X130 (SIM) |
LD0 |
XSGGIO130 |
|
RTD (X130) 6RTD and 2mA |
X130 (RTD) |
LD0 |
XRGGIO130 |
XRGGIO130 |
BIO (X130) card |
X130 (BIO) |
LD0 |
XGGIO130 |
XGGIO130 |
COM (X000) card |
XGGIO90 |
LD0 |
XGGIO90 |
XGGIO90 |
LED indication control |
LEDPTRC |
LD0 |
LEDPTRC |
LEDPTRC |
Programmable LEDs |
LED |
LD0 |
LEDGGIO |
LEDGGIO |
Note: For more information on the implementation of IEC 61850 in protection relays, see IEC 61850 engineering guide and conformance documents.
1 IEC61850 Edition1 logical node is GNRLLTMM