| Function | IEC 61850 | Logical device | Logical nodes in Ver.5.0 FP1 | Logical nodes in Ver.5.0 or older |
|---|---|---|---|---|
| Protection | ||||
|
Protection LLN0 |
Protection |
LD0 |
LLN0 LPHD LINF LDEV |
LLN0 LPHD IHMI GSAL |
|
Three-phase non-directional overcurrent protection, low stage |
PHLPTOC |
LD0 |
PHLPTOC |
PHLPTOC |
|
Three-phase non-directional overcurrent protection, low stage |
FPHLPTOC |
LD0 |
FPHLPTOC |
FPHLPTOC |
|
Three-phase non-directional overcurrent protection, high stage |
PHHPTOC |
LD0 |
PHHPTOC |
PHHPTOC |
|
Three-phase non-directional overcurrent protection, instantaneous stage |
PHIPTOC |
LD0 |
PHIPTOC |
PHIPTOC |
|
Three-phase directional overcurrent protection, low stage |
DPHLPDOC |
LD0 |
DPHLPTOC DPHLRDIR |
DPHLPTOC DPHLRDIR |
|
Three-phase directional overcurrent protection, low stage |
FDPHLPDOC |
LD0 |
FDPHLPTOC DPHLRDIR FDPHLRDIR |
FDPHLPTOC DPHLRDIR FDPHLRDIR |
|
Three-phase directional overcurrent protection, high stage |
DPHHPDOC |
LD0 |
DPHHPTOC DPHHRDIR |
DPHHPTOC DPHHRDIR |
|
Non-directional earth-fault protection, low stage |
EFLPTOC |
LD0 |
EFLPTOC |
EFLPTOC |
|
Non-directional earth-fault protection, high stage |
EFHPTOC |
LD0 |
EFHPTOC |
EFHPTOC |
|
Non-directional earth-fault protection, instantaneous stage |
EFIPTOC |
LD0 |
EFIPTOC |
EFIPTOC |
|
Directional earth-fault protection, low stage |
DEFLPDEF |
LD0 |
DEFLPTOC DEFLRDIR |
DEFLPTOC DEFLRDIR |
|
Directional earth-fault protection, low stage |
FDEFLPDEF |
LD0 |
FDEFLPTOC FDEFLRDIR |
FDPHLPTOC DPHLRDIR FDPHLRDIR |
|
Directional earth-fault protection, high stage |
DEFHPDEF |
LD0 |
DEFHPTOC DEFHRDIR |
DEFHPTOC DEFHRDIR |
|
Admittance-based earth-fault protection |
EFPADM |
LD0 |
EFPADM |
EFPADM |
|
Wattmetric-based earth-fault protection |
WPWDE |
LD0 |
WRDIR WPSDE WMMXU |
WRDIR WPSDE WMMXU |
|
Transient/intermittent earth-fault protection |
INTRPTEF |
LD0 |
INTRPTEF |
INTRPTEF |
|
Harmonics-based earth-fault protection |
HAEFPTOC |
LD0 |
HAEFPTOC HAEFMHAI |
HAEFPTOC HAEFMHAI |
|
Multifrequency admittance-based earth-fault protection |
MFADPSDE |
LD0 |
MFADPSDE MFADRDIR |
|
|
Non-directional (cross-country) earth-fault protection, using calculated Io |
EFHPTOC |
LD0 |
EFHPTOC |
EFHPTOC |
|
Negative-sequence overcurrent protection |
NSPTOC |
LD0 |
NSPTOC |
NSPTOC |
|
Phase discontinuity protection |
PDNSPTOC |
LD0 |
PDNSPTOC |
PDNSPTOC |
|
Residual overvoltage protection |
ROVPTOV |
LD0 |
ROVPTOV |
ROVPTOV |
|
Three-phase undervoltage protection |
PHPTUV |
LD0 |
PHPTUV |
PHPTUV |
|
Three-phase overvoltage protection |
PHPTOV |
LD0 |
PHPTOV |
PHPTOV |
|
Positive-sequence undervoltage protection |
PSPTUV |
LD0 |
PSPTUV |
PSPTUV |
|
Negative-sequence overvoltage protection |
NSPTOV |
LD0 |
NSPTOV |
NSPTOV |
|
Loss of phase (undercurrent) |
PHPTUC |
LD0 |
PHPTUC |
|
|
Frequency protection |
FRPFRQ |
LD0 |
FRPTRC FRPTOF FRPTUF FRPFRC |
FRPTRC FRPTOF FRPTUF FRPFRC |
|
Three-phase thermal protection for feeders, cables and distribution transformers |
T1PTTR |
LD0 |
T1PTTR |
T1PTTR |
|
Circuit breaker failure protection |
CCBRBRF |
LD0 |
CCBRBRF |
CCBRBRF |
|
Three-phase inrush detector |
INRPHAR |
LD0 |
INRPHAR |
INRPHAR |
|
Master trip |
TRPPTRC |
LD0 |
TRPPTRC |
TRPPTRC |
|
Multipurpose protection |
MAPGAPC |
LD0 |
MAPGAPC |
MAPGAPC |
|
Load-shedding and restoration |
LSHDPFRQ |
LD0 |
LSHDPTRC LSHDPTOF LSHDPTUF LSHDPFRC |
LSHDPTRC LSHDPTUF LSHDPFRC |
|
Fault locator |
SCEFRFLO |
LD0 |
SCEFRFLO SCEFZLIN SCEF2ZLIN SCEF3ZLIN FLORFRC |
SCEFRFLO FLOMSTA |
|
Phase power directional function |
DPSRDIR |
LD0 |
DPSRDIR |
|
| Power quality | ||||
|
Current total demand distortion |
CMHAI |
LD0 |
CMHAI |
CMHAI |
|
Voltage total harmonic distortion |
VMHAI |
LD0 |
VMHAI |
VMHAI |
|
Voltage variation |
PHQVVR |
LD0 |
PHQVVR PH2QVVR PH3QVVR QVVRQRC QVV2RQRC QVV3RQRC |
PHQVVR PH2QVVR PH3QVVR QVVMSTA QVV2MSTA QVV3MSTA |
|
Voltage unbalance |
VSQVUB |
LD0 |
VSQVUB QVU1RQRC QVU2RQRC QVU3RQRC |
|
| Control | ||||
|
Local/remote control function block |
Control |
CTRL |
LLN0 LPHD1 |
LLN0 LPHD1 |
|
Circuit breaker control |
CBXCBR |
CTRL |
CBCSWI CBCILO CBXCBR |
CBCSWI CBCILO CBXCBR |
|
Disconnector control |
DCXSWI |
CTRL |
DCCSWI DCCILO DCXSWI |
DCCSWI DCCILO DCXSWI |
|
Disconnector position indication |
DCSXSWI |
CTRL |
DCSXSWI |
DCSXSWI |
|
Earthing switch indication |
ESSXSWI |
CTRL |
ESSXSWI |
ESSXSWI |
|
Autoreclosing |
DARREC |
LD0 |
DARREC |
DARREC |
|
Synchronism and energizing check |
SECRSYN |
LD0 |
SECRSYN |
SECRSYN |
|
Automatic transfer switch |
ATSABTC |
LD0 |
ATSABTC |
ATSABTC |
| Condition monitoring | ||||
|
Circuit-breaker condition monitoring |
SSCBR1 |
LD0 |
SSCBR1 SPH1SCBR SPH2SCBR SPH3SCBR SSOPM SSIMG |
SSCBR1 |
|
Trip circuit supervision |
TCSSCBR |
LD0 |
TCSSCBR |
TCSSCBR |
|
Current circuit supervision |
CCSPVC |
LD0 |
CCSPVC |
CCRDIF |
|
Fuse failure supervision |
SEQSPVC |
LD0 |
SEQSPVC |
SEQRFUF |
|
Runtime counter for machines and devices |
MDSOPT |
LD0 |
MDSOPT |
MDSOPT |
|
Voltage presence |
PHSVPR |
LD0 |
PHSVPR |
PHSVPR |
| Measurement | ||||
|
Disturbance recorder |
RDRE |
LD0 |
DR_LLN0 RDRE_type RADR_type RBDR_type LPHD_M |
DR_LLN0 RDRE_type RADR_type RBDR_type LPHD_M |
|
Load profile record |
LDPRLRC |
LD0 |
LDPRLRC |
LDPMSTA |
|
Fault record |
FLTRFRC |
LD0 |
FLTRFRC |
FLTMSTA |
|
Three-phase current measurement |
CMMXU |
LD0 |
CMMXU CAVMMXU CMAMMXU CMIMMXU |
CMMXU CMSTA |
|
Phase sequence current measurement |
CSMSQI |
LD0 |
CSMSQI |
CSMSQI |
|
Residual current measurement |
RESCMMXU |
LD0 |
RESCMMXU RCAVMMXU RCMAMMXU RCMIMMXU |
RESCMMXU RESCMSTA |
|
Three-phase voltage measurement |
VMMXU |
LD0 |
VMMXU VAVMMXU |
VMMXU VMSTA |
|
Residual voltage measurement |
RESVMMXU |
LD0 |
RESVMMXU RVAVMMXU RVMAMMXU RVMIMMXU |
RESVMMXU RESVMSTA |
|
Phase sequence voltage measurement |
VSMSQI |
LD0 |
VSMSQI |
VSMSQI |
|
Three-phase power and energy measurement |
PEMMXU |
LD0 |
PEMMXU PEMMTR PEAVMMXU PEMAMMXU PEMIMMXU |
PEMMXU PEMMTR PEMSTA |
|
Single-phase power and energy measurement |
SPEMMXU |
LD0 |
SPEMMXU SPE1MMTR SPE2MMTR SPE3MMTR SPEAVMMXU SPEMAMMXU SPEMIMMXU |
|
|
Frequency measurement |
FMMXU |
LD0 |
FMMXU |
FMMXU |
|
RTD/mA measurement X130 (AIM+RTD) |
XARGGIO130 |
LD0 |
XARGGIO130 |
XARGGIO130 |
| Instrument transformers and sensors | ||||
|
Three-phase current transformer |
ILTCTR |
LD0 |
IL1TCTR IL2TCTR IL3TCTR |
IL1TCTR IL2TCTR IL3TCTR |
|
Three-phase voltage transformer |
ULTVTR |
LD0 |
UL1TVTR UL2TVTR UL3TVTR |
UL1TVTR UL2TVTR UL3TVTR |
|
Residual current transformer |
RESTCTR |
LD0 |
RESTCTR |
RESTCTR |
|
Residual voltage transformer |
RESTVTR |
LD0 |
RESTVTR |
RESTVTR |
| Communication | ||||
|
IEC 61850-9-2 LE sampled value sending |
SMVSENDER |
MU01 |
LLN0 LPHD1 I01ATCTR1 I01BTCTR2 I01CTCTR3 I01NTCTR4 U01ATVTR1 U01BTVTR2 U01CTVTR3 U01NTVTR4 |
LLN0 LPHD1 I01ATCTR1 I01BTCTR2 I01CTCTR3 I01NTCTR4 U01ATVTR1 U01BTVTR2 U01CTVTR3 U01NTVTR4 |
|
IEC 61850-9-2 LE sampled value receiving (voltage sharing) |
SMVRCV |
MU01 |
SMVLSVS |
|
|
Redundant Ethernet channel supervision |
RCHLCCH |
LD0 |
RCHLCCH |
|
|
Ethernet channel supervision |
SCHLCCH |
LD0 |
SCHLCCH |
|
|
Serial port supervision |
SERLCCH |
LD0 |
SERLCCH |
|
|
Human machine interface |
IHMI |
LD0 |
IHMI |
IHMI |
|
General security application |
GSAL |
LD0 |
GSAL |
GSAL |
|
Time synchronization and local time |
GNRLLTMS |
LD0 |
GNRLLTMS 1 GNRLLTIM |
GNRLLTMS |
| Controllable logic | ||||
|
Minimum pulse timer |
TPGAPC |
TPGAPC |
TPGAPC |
|
|
Minimum pulse timer |
TPSGAPC |
TPSGAPC |
TPSGAPC |
|
|
Minimum pulse timer |
TPMGAPC |
TPMGAPC |
TPMGAPC |
|
|
Pulse timer |
PTGAPC |
PTGAPC |
PTGAPC |
|
|
Time delay off |
TOFGAPC |
TOFGAPC |
TOFGAPC |
|
|
Time delay on |
TONGAPC |
TONGAPC |
TONGAPC |
|
|
Set-reset |
SRGAPC |
SRGAPC |
SRGAPC |
|
|
Move |
MVGAPC |
MVGAPC |
MVGAPC |
|
|
Generic control point |
SPCGAPC |
SPCGAPC |
SPCGGIO |
|
|
Remote generic control points |
SPCRGAPC |
LD0 |
SPCRGAPC |
SPCRGAPC |
|
Local generic control points |
SPCLGAPC |
LD0 |
SPCLGAPC |
SPCLGAPC |
|
Generic up-down counters |
UDFCNT |
LD0 |
UDFCNT |
UDFCNT |
|
Analog value scaling |
SCA4GAPC |
SCA4GAPC |
SCA4GAPC |
|
|
Integer value move |
MVI4GAPC |
MVI4GAPC |
MVI4GAPC |
|
|
Daily timer function |
DTMGAPC |
LD0 |
DTMGAPC |
|
|
Programmable buttons (4 buttons) |
FKEY4GGIO |
LD0 |
FKEY4GGIO |
|
| Protocols | ||||
|
IEC 61850 |
MMSLPRT |
LD0 |
MMSLPRT |
MMSGGIO |
|
GOOSE |
GSELPRT |
LD0 |
GSELPRT |
GSEGGIO |
|
MODBUS |
MBSLPRT |
LD0 |
MBSLPRT |
MBSLPRT |
|
DNP 3.0 |
DNPLPRT |
LD0 |
DNPLPRT |
DNPLPRT |
|
IEC 101/104 |
I5CLPRT |
LD0 |
I5CLPRT |
I5CLPRT |
| Hardware | ||||
|
PSM (X100) card |
X100 (PSM) |
LD0 |
XGGIO100 |
XGGIO100 |
|
BIO (X110) card |
X110 (BIO) |
LD0 |
XGGIO110 |
XGGIO110 |
|
AIM (X120) 4CT with Io |
X120 (AIM) |
LD0 |
XGGIO120 |
XGGIO120 |
|
AIM (X120) 4CT with Uo |
X120 (AIM) |
LD0 |
XGGIO120 |
XGGIO120 |
|
AIM (X120) 7CT with Io |
X120 (AIM2) |
LD0 |
XAGGIO120 |
XAGGIO120 |
|
AIM (X120) 4CT_3VT with sensitive Io |
X120 (AIM2) |
LD0 |
XAGGIO120 |
XAGGIO120 |
|
AIM (X130) 5 VT |
X130 (AIM) |
LD0 |
XAGGIO130 |
XAGGIO130 |
|
AIM (X130) 5 VT, 2RTD and 1mA |
X130 (AIM +RTD) |
LD0 |
XARGGIO130 |
XARGGIO130 |
|
SIM (X130) sensor input module |
X130 (SIM) |
LD0 |
XSGGIO130 |
XSGGIO130 |
|
SIM (X130) 3Is_3Us with sensitive Io |
X130 (SIM) |
LD0 |
XSGGIO130 |
XSGGIO130 |
|
SIM (X130) 3Is_3Us_3VT with sensitive Io |
X130 (SIM) |
LD0 |
XSGGIO130 |
|
|
RTD (X130) 6RTD and 2mA |
X130 (RTD) |
LD0 |
XRGGIO130 |
XRGGIO130 |
|
BIO (X130) card |
X130 (BIO) |
LD0 |
XGGIO130 |
XGGIO130 |
|
COM (X000) card |
XGGIO90 |
LD0 |
XGGIO90 |
XGGIO90 |
|
LED indication control |
LEDPTRC |
LD0 |
LEDPTRC |
LEDPTRC |
|
Programmable LEDs |
LED |
LD0 |
LEDGGIO |
LEDGGIO |
Note: For more information on the implementation of IEC 61850 in protection relays, see IEC 61850 engineering guide and conformance documents.
1 IEC61850 Edition1 logical node is GNRLLTMM