All available functions are listed in the table. All of them may not be applicable to all products.
Function | IEC 61850 | IEC 60617 | IEC-ANSI |
---|---|---|---|
Protection | |||
Three-phase non-directional overcurrent protection, low stage, instance 1 |
PHLPTOC1 |
3I> (1) |
51P-1 (1) |
FPHLPTOC1 |
F3I> (1) |
F51P-1 (1) |
|
Three-phase non-directional overcurrent protection, high stage, instance 1 |
PHHPTOC1 |
3I>> (1) |
51P-2 (1) |
Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 |
PHIPTOC1 |
3I>>> (1) |
50P/51P (1) |
Three-phase non-directional overcurrent protection, instantaneous stage, instance 2 |
PHIPTOC2 |
3I>>> (2) |
50P/51P (2) |
Three-phase directional overcurrent protection, low stage, instance 1 |
DPHLPDOC1 |
3I> -> (1) |
67-1 (1) |
FDPHLPDOC1 |
F3I> -> (1) |
F67-1 (1) |
|
Three-phase directional overcurrent protection, low stage, instance 2 |
DPHLPDOC2 |
3I> -> (2) |
67-1 (2) |
FDPHLPDOC2 |
F3I> -> (2) |
F67-1 (2) |
|
Three-phase directional overcurrent protection, low stage, instance 3 |
DPHLPDOC3 |
3I> -> (3) |
67-1 (3) |
Three-phase directional overcurrent protection, low stage, instance 4 |
DPHLPDOC4 |
3I> -> (4) |
67-1 (4) |
Three-phase directional overcurrent protection, high stage, instance 1 |
DPHHPDOC1 |
3I>> -> (1) |
67-2 (1) |
Three-phase directional overcurrent protection, high stage, instance 2 |
DPHHPDOC2 |
3I>> -> (2) |
67-2 (2) |
Three-phase directional overcurrent protection, high stage, instance 3 |
DPHHPDOC3 |
3I>> -> (3) |
67-2 (3) |
Three-phase directional overcurrent protection, high stage, instance 4 |
DPHHPDOC4 |
3I>> -> (4) |
67-2 (4) |
Non-directional earth-fault protection, low stage, instance 1 |
EFLPTOC1 |
Io> (1) |
51N-1 (1) |
FEFLPTOC1 |
FIo> (1) |
F51N-1 (1) |
|
Non-directional earth-fault protection, high stage, instance 1 |
EFHPTOC1 |
Io>> (1) |
51N-2 (1) |
Non-directional earth-fault protection, instantaneous stage, instance 1 |
EFIPTOC1 |
Io>>> (1) |
50N/51N (1) |
Directional earth-fault protection, low stage, instance 1 |
DEFLPDEF1 |
Io> -> (1) |
67N-1 (1) |
FDEFLPDEF1 |
FIo> -> (1) |
F67N-1 (1) |
|
Directional earth-fault protection, low stage, instance 2 |
DEFLPDEF2 |
Io> -> (2) |
67N-1 (2) |
FDEFLPDEF2 |
FIo> -> (2) |
F67N-1 (2) |
|
Directional earth-fault protection, low stage, instance 3 |
DEFLPDEF3 |
Io> -> (3) |
67N-1 (3) |
Directional earth-fault protection, low stage, instance 4 |
DEFLPDEF4 |
Io> -> (4) |
67N-1 (4) |
Directional earth-fault protection, high stage, instance 1 |
DEFHPDEF1 |
Io>> -> (1) |
67N-2 (1) |
Directional earth-fault protection, high stage, instance 2 |
DEFHPDEF2 |
Io>> -> (2) |
67N-2 (2) |
Directional earth-fault protection, high stage, instance 3 |
DEFHPDEF3 |
Io>> -> (3) |
67N-2 (3) |
Directional earth-fault protection, high stage, instance 4 |
DEFHPDEF4 |
Io>> -> (4) |
67N-2 (4) |
Transient / intermittent earth-fault protection, instance 1 |
INTRPTEF1 |
Io> -> IEF (1) |
67NIEF (1) |
Admittance-based earth-fault protection, instance 1 |
EFPADM1 |
Yo> -> (1) |
21YN (1) |
Admittance-based earth-fault protection, instance 2 |
EFPADM2 |
Yo> -> (2) |
21YN (2) |
Admittance-based earth-fault protection, instance 3 |
EFPADM3 |
Yo> -> (3) |
21YN (3) |
Wattmetric-based earth-fault protection, instance 1 |
WPWDE1 |
Po> -> (1) |
32N (1) |
Wattmetric-based earth-fault protection, instance 2 |
WPWDE2 |
Po> -> (2) |
32N (2) |
Wattmetric-based earth-fault protection, instance 3 |
WPWDE3 |
Po> -> (3) |
32N (3) |
Harmonics-based earth-fault protection, instance 1 |
HAEFPTOC1 |
Io>HA (1) |
51NHA (1) |
Multifrequency admittance-based earth-fault protection, instance 1 |
MFADPSDE1 |
Io> -> Y (1) |
67YN (1) |
Multifrequency admittance-based earth-fault protection, instance 2 |
MFADPSDE2 |
Io> -> Y (2) |
67YN (2) |
Negative-sequence overcurrent protection, instance 1 |
NSPTOC1 |
I2> (1) |
46 (1) |
Negative-sequence overcurrent protection, instance 2 |
NSPTOC2 |
I2> (2) |
46 (2) |
Phase discontinuity protection, instance 1 |
PDNSPTOC1 |
I2/I1> (1) |
46PD (1) |
Residual overvoltage protection, instance 1 |
ROVPTOV1 |
Uo> (1) |
59G (1) |
Residual overvoltage protection, instance 2 |
ROVPTOV2 |
Uo> (2) |
59G (2) |
Three-phase undervoltage protection, instance 1 |
PHPTUV1 |
3U< (1) |
27 (1) |
Three-phase undervoltage protection, instance 2 |
PHPTUV2 |
3U< (2) |
27 (2) |
Three-phase undervoltage protection, instance 3 |
PHPTUV3 |
3U< (3) |
27 (3) |
Three-phase overvoltage protection, instance 1 |
PHPTOV1 |
3U> (1) |
59 (1) |
Three-phase overvoltage protection, instance 2 |
PHPTOV2 |
3U> (2) |
59 (2) |
Three-phase overvoltage protection, instance 3 |
PHPTOV3 |
3U> (3) |
59 (3) |
Positive-sequence undervoltage protection, instance 1 |
PSPTUV1 |
U1< (1) |
47U+ (1) |
Negative-sequence overvoltage protection, instance 1 |
NSPTOV1 |
U2> (1) |
47O- (1) |
Loss of phase (undercurrent), instance 1 |
PHPTUC1 |
3I< (1) |
37 (1) |
Loss of phase (undercurrent), instance 2 |
PHPTUC2 |
3I< (2) |
37 (2) |
Frequency protection, instance 1 |
FRPFRQ1 |
f>/f<,df/dt (1) |
81 (1) |
Frequency protection, instance 2 |
FRPFRQ2 |
f>/f<,df/dt (2) |
81 (2) |
Three-phase thermal protection for feeders, cables and distribution transformers, instance 1 |
T1PTTR1 |
3Ith>F (1) |
49F (1) |
Circuit breaker failure protection, instance 1 |
CCBRBRF1 |
3I>/Io>BF (1) |
51BF/51NBF (1) |
Circuit breaker failure protection, instance 2 |
CCBRBRF2 |
3I>/Io>BF (2) |
51BF/51NBF (2) |
Three-phase inrush detector, instance 1 |
INRPHAR1 |
3I2f> (1) |
68 (1) |
Master trip, instance 1 |
TRPPTRC1 |
Master Trip (1) |
94/86 (1) |
Master trip, instance 2 |
TRPPTRC2 |
Master Trip (2) |
94/86 (2) |
Multipurpose protection, instance 1 |
MAPGAPC1 |
MAP (1) |
MAP (1) |
Multipurpose protection, instance 2 |
MAPGAPC2 |
MAP (2) |
MAP (2) |
Multipurpose protection, instance 3 |
MAPGAPC3 |
MAP (3) |
MAP (3) |
Multipurpose protection, instance 4 |
MAPGAPC4 |
MAP (4) |
MAP (4) |
Multipurpose protection, instance 5 |
MAPGAPC5 |
MAP (5) |
MAP (5) |
Multipurpose protection, instance 6 |
MAPGAPC6 |
MAP (6) |
MAP (6) |
Load-shedding and restoration, instance 1 |
LSHDPFRQ1 |
UFLS/R (1) |
81LSH (1) |
Load-shedding and restoration, instance 2 |
LSHDPFRQ2 |
UFLS/R (2) |
81LSH (2) |
Fault locator, instance 1 |
SCEFRFLO1 |
FLOC (1) |
21FL (1) |
Three-phase power directional element, instance 1 |
DPSRDIR1 |
I1-> (1) |
32P (1) |
Three-phase power directional element, instance 2 |
DPSRDIR2 |
I1-> (2) |
32P (2) |
Power quality | |||
Current total demand distortion, instance 1 |
CMHAI1 |
PQM3I (1) |
PQM3I (1) |
Voltage total harmonic distortion, instance 1 |
VMHAI1 |
PQM3U (1) |
PQM3V (1) |
Voltage variation, instance 1 |
PHQVVR1 |
PQMU (1) |
PQMV (1) |
Voltage unbalance, instance 1 |
VSQVUB1 |
PQUUB (1) |
PQVUB (1) |
Control | |||
Circuit-breaker control, instance 1 |
CBXCBR1 |
I <-> O CB (1) |
I <-> O CB (1) |
Circuit-breaker control, instance 2 |
CBXCBR2 |
I <-> O CB (2) |
I <-> O CB (2) |
Disconnector control, instance 1 |
DCXSWI1 |
I <-> O DCC (1) |
I <-> O DCC (1) |
Disconnector control, instance 2 |
DCXSWI2 |
I <-> O DCC (2) |
I <-> O DCC (2) |
Disconnector control, instance 3 |
DCXSWI3 |
I <-> O DCC (3) |
I <-> O DCC (3) |
Disconnector control, instance 4 |
DCXSWI4 |
I <-> O DCC (4) |
I <-> O DCC (4) |
Disconnector control, instance 5 |
DCXSWI5 |
I <-> O DCC (5) |
I <-> O DCC (5) |
Disconnector control, instance 6 |
DCXSWI6 |
I <-> O DCC (6) |
I <-> O DCC (6) |
Disconnector control, instance 7 |
DCXSWI7 |
I <-> O DCC (7) |
I <-> O DCC (7) |
Disconnector control, instance 8 |
DCXSWI8 |
I <-> O DCC (8) |
I <-> O DCC (8) |
Disconnector position indication, instance 1 |
DCSXSWI1 |
I <-> O DC (1) |
I <-> O DC (1) |
Disconnector position indication, instance 2 |
DCSXSWI2 |
I <-> O DC (2) |
I <-> O DC (2) |
Earthing switch indication, instance 1 |
ESSXSWI1 |
I <-> O ES (1) |
I <-> O ES (1) |
Earthing switch indication, instance 2 |
ESSXSWI2 |
I <-> O ES (2) |
I <-> O ES (2) |
Earthing switch indication, instance 3 |
ESSXSWI3 |
I <-> O ES (3) |
I <-> O ES (3) |
Earthing switch indication, instance 4 |
ESSXSWI4 |
I <-> O ES (4) |
I <-> O ES (4) |
Earthing switch indication, instance 5 |
ESSXSWI5 |
I <-> O ES (5) |
I <-> O ES (5) |
Earthing switch indication, instance 6 |
ESSXSWI6 |
I <-> O ES (6) |
I <-> O ES (6) |
Earthing switch indication, instance 7 |
ESSXSWI7 |
I <-> O ES (7) |
I <-> O ES (7) |
Earthing switch indication, instance 8 |
ESSXSWI8 |
I <-> O ES (8) |
I <-> O ES (8) |
Autoreclosing, instance 1 |
DARREC1 |
O -> I (1) |
79 (1) |
Autoreclosing, instance 2 |
DARREC2 |
O -> I (2) |
79 (2) |
Synchronism and energizing check, instance 1 |
SECRSYN1 |
SYNC (1) |
25 (1) |
Automatic transfer switch, instance 1 |
ATSABTC1 |
ATSABTC1 |
ATSABTC1 |
Condition monitoring | |||
Circuit-breaker condition monitoring, instance 1 |
SSCBR1 |
CBCM (1) |
CBCM (1) |
Circuit-breaker condition monitoring, instance 2 |
SSCBR2 |
CBCM (2) |
CBCM (2) |
Trip circuit supervision, instance 1 |
TCSSCBR1 |
TCS (1) |
TCM (1) |
Trip circuit supervision, instance 2 |
TCSSCBR2 |
TCS (2) |
TCM (2) |
Fuse failure supervision, instance 1 |
SEQSPVC1 |
FUSEF (1) |
60 (1) |
Fuse failure supervision, instance 2 |
SEQSPVC2 |
FUSEF (1) |
60 (1) |
Runtime counter for machines and devices, instance 1 |
MDSOPT1 |
OPTS (1) |
OPTM (1) |
Voltage presence, instance 1 |
PHSVPR1 |
PHSVPR(1) |
PHSVPR(1) |
Voltage presence, instance 2 |
PHSVPR2 |
PHSVPR(2) |
PHSVPR(2) |
Measurement | |||
Three-phase current measurement, instance 1 |
CMMXU1 |
3I (1) |
3I (1) |
Three-phase current measurement, instance 2 |
CMMXU2 |
3I (2) |
3I (2) |
Sequence current measurement, instance 1 |
CSMSQI1 |
I1, I2, I0 (1) |
I1, I2, I0 (1) |
Sequence current measurement, instance 2 |
CSMSQI2 |
I1, I2, I0 (2) |
I1, I2, I0 (2) |
Residual current measurement, instance 1 |
RESCMMXU1 |
Io (1) |
In (1) |
Three-phase voltage measurement, instance 1 |
VMMXU1 |
3U (1) |
3V (1) |
Three-phase voltage measurement, instance 2 |
VMMXU2 |
3U (2) |
3V (2) |
Residual voltage measurement, instance 1 |
RESVMMXU1 |
Uo (1) |
Vn (1) |
Sequence voltage measurement, instance 1 |
VSMSQI1 |
U1, U2, U0 (1) |
V1, V2, V0 (1) |
Sequence voltage measurement, instance 2 |
VSMSQI2 |
U1, U2, U0 (2) |
V1, V2, V0 (2) |
Three-phase power and energy measurement, instance 1 |
PEMMXU1 |
P, E (1) |
P, E (1) |
Three-phase power and energy measurement, instance 2 |
PEMMXU2 |
P, E (2) |
P, E (2) |
Single-phase power and energy measurement, instance 1 |
SPEMMXU1 |
SP, SE (1) |
SP, SE (1) |
Single-phase power and energy measurement, instance 2 |
SPEMMXU2 |
SP, SE (2) |
SP, SE (2) |
Frequency measurement, instance 1 |
FMMXU1 |
f (1) |
f (1) |
Frequency measurement, instance 2 |
FMMXU2 |
f (2) |
f (2) |
Load profile record, instance 1 |
LDPRLRC1 |
LOADPROF (1) |
LOADPROF (1) |
Other | |||
Minimum pulse timer (2 pcs), instance 1 |
TPGAPC1 |
TP (1) |
TP (1) |
Minimum pulse timer (2 pcs), instance 2 |
TPGAPC2 |
TP (2) |
TP (2) |
Minimum pulse timer (2 pcs, second resolution), instance 1 |
TPSGAPC1 |
TPS (1) |
TPS (1) |
Minimum pulse timer (2 pcs, minute resolution), instance 1 |
TPMGAPC1 |
TPM (1) |
TPM (1) |
Pulse timer (8 pcs), instance 1 |
PTGAPC1 |
PT (1) |
PT (1) |
Pulse timer (8 pcs), instance 2 |
PTGAPC2 |
PT (2) |
PT (2) |
Time delay off (8 pcs), instance 1 |
TOFGAPC1 |
TOF (1) |
TOF (1) |
Time delay off (8 pcs), instance 2 |
TOFGAPC2 |
TOF (2) |
TOF (2) |
Time delay on (8 pcs), instance 1 |
TONGAPC1 |
TON (1) |
TON (1) |
Time delay on (8 pcs), instance 2 |
TONGAPC2 |
TON (2) |
TON (2) |
Set-reset (8 pcs), instance 1 |
SRGAPC1 |
SR (1) |
SR (1) |
Set-reset (8 pcs), instance 2 |
SRGAPC2 |
SR (2) |
SR (2) |
Move (8 pcs), instance 1 |
MVGAPC1 |
MV (1) |
MV (1) |
Move (8 pcs), instance 2 |
MVGAPC2 |
MV (2) |
MV (2) |
Move (8 pcs), instance 3 |
MVGAPC3 |
MV (3) |
MV (3) |
Move (8 pcs), instance 4 |
MVGAPC4 |
MV (4) |
MV (4) |
Move (8 pcs), instance 5 |
MVGAPC5 |
MV (5) |
MV (5) |
Move (8 pcs), instance 6 |
MVGAPC6 |
MV (6) |
MV (6) |
Move (8 pcs), instance 7 |
MVGAPC7 |
MV (7) |
MV (7) |
Move (8 pcs), instance 8 |
MVGAPC8 |
MV (8) |
MV (8) |
Generic control point (16 pcs), instance 1 |
SPCGAPC1 |
SPC (1) |
SPC (1) |
Generic control point (16 pcs), instance 2 |
SPCGAPC2 |
SPC (2) |
SPC (2) |
Remote generic control points, instance 1 |
SPCRGAPC1 |
SPCR (1) |
SPCR (1) |
Local generic control points, instance 1 |
SPCLGAPC1 |
SPCL (1) |
SPCL (1) |
Generic up-down counters, instance 1 |
UDFCNT1 |
UDCNT (1) |
UDCNT (1) |
Generic up-down counters, instance 2 |
UDFCNT2 |
UDCNT (2) |
UDCNT (2) |
Generic up-down counters, instance 3 |
UDFCNT3 |
UDCNT (3) |
UDCNT (3) |
Analog value scaling, instance 1 |
SCA4GAPC1 |
SCA4 (1) |
SCA4 (1) |
Analog value scaling, instance 2 |
SCA4GAPC2 |
SCA4 (2) |
SCA4 (2) |
Analog value scaling, instance 3 |
SCA4GAPC3 |
SCA4 (3) |
SCA4 (3) |
Analog value scaling, instance 4 |
SCA4GAPC4 |
SCA4 (4) |
SCA4 (4) |
Analog value scaling, instance 5 |
SCA4GAPC5 |
SCA4 (5) |
SCA4 (5) |
Analog value scaling, instance 6 |
SCA4GAPC6 |
SCA4 (6) |
SCA4 (6) |
Analog value scaling, instance 7 |
SCA4GAPC7 |
SCA4 (7) |
SCA4 (7) |
Analog value scaling, instance 8 |
SCA4GAPC8 |
SCA4 (8) |
SCA4 (8) |
Analog value scaling, instance 9 |
SCA4GAPC9 |
SCA4 (9) |
SCA4 (9) |
Analog value scaling, instance 10 |
SCA4GAPC10 |
SCA4 (10) |
SCA4 (10) |
Analog value scaling, instance 11 |
SCA4GAPC11 |
SCA4 (11) |
SCA4 (11) |
Analog value scaling, instance 12 |
SCA4GAPC12 |
SCA4 (12) |
SCA4 (12) |
Integer value move, instance 1 |
MVI4GAPC1 |
MVI4 (1) |
MVI4 (1) |
Integer value move, instance 2 |
MVI4GAPC2 |
MVI4 (2) |
MVI4 (2) |
Daily timer function, instance 1 |
DTMGAPC1 |
DTMGAPC1 |
DTMGAPC1 |
Daily timer function, instance 2 |
DTMGAPC2 |
DTMGAPC2 |
DTMGAPC2 |
Programmable buttons (4 buttons) |
FKEY4GGIO1 |
FKEY4GGIO1 |
FKEY4GGIO1 |
Logging functions | |||
Disturbance recorder |
RDRE1 |
DR (1) |
DFR (1) |
Fault record |
FLTRFRC1 |
FAULTREC (1) |
FAULTREC (1) |