REC615 and RER615 Engineering Manual

The physical outputs to process can be blocked with “Blocked” mode. If physical outputs need to be blocked, the application configuration must block signals or function blocks that affect primary apparatuses. Blocking scheme needs to use BEH_BLK output of CONTROL function block.
Figure 1. Circuit breaker control CBXCBR1 blocked using Protection function block BEH_BLK output
image/svg+xmlCBXCBR1POSOPENPOSCLOSEENA_OPENENA_CLOSEBLK_OPENBLK_CLOSEAU_OPENAU_CLOSETRIPSYNC_OKSYNC_ITL_BYPSELECTEDEXE_OPEXE_CLOP_REQCL_REQOPENPOSCLOSEPOSOKPOSOPEN_ENADCLOSE_ENADControlCTRL_OFFCTRL_LOCCTRL_STACTRL_REMCTRL_ALLOFFLOCALSTATIONREMOTEALLBEH_TESTBEH_BLKANDB1B2OANDB1B2ONOTINOUTNOTINOUTFALSEX120_BI3_CB_OPENEDX120_BI2_CB_CLOSEDCBXCBR1_ENA_CLOSETRUECBXCBR1_AU_OPENCBXCBR1_AU_CLOSECBXCBR1_OPENPOSCONTROL_LOCALCONTROL_REMOTECBXCBR1_EXE_OPCBXCBR1_EXE_CL