Checking and updating Modbus points - Grid automation - Engineering Manual - REC615 Grid Automation - RER615 Grid Automation Protection and Control - Relion 615 series - 2.0 - IEC - ANSI - 28.04.2023

REC615 and RER615 Engineering Manual

If Modbus is used, the migrated Modbus point list should for most part correspond to the configuration made in the old IED.
  1. Check the point list and verify that all the point types correspond to the old configuration and Modbus master.
    • 0X – Readable coils
    • 1X – Discrete inputs
    • 3X – Input registers
    • 4X - Readable holding registers
    • Fault record data
    If some points have different attributes, adjust them in the Communication Management tool.
  2. Adjust possible missing points or changed point addresses in Modbus master configuration.